ELECTRO
CHEMICAL DUTY RECTIFIER
Up to 300,000 Amps - 6, 12, 24 Pulse units
Quality and Fast Delivery
 |
|
Facility
in Production
|
Neeltran manufactures its own rectifiers
and oil cooled rectifier transformers
General
Specifications
D.C.
Rating: Output up to 300,000 amps, 1500 volts
Primary
A.C. voltage: Any standard 3 phase supply up to
34 Kv 50/60 Hz
Duty:
100% continuous
Regulation:
± 1% current (options available)

Enclosures:
Metal, Aluminum or Fiberglass
Indoor
- Nema 1, Nema 12 (I.P. 20)
Outdoor - Nema 3S, 3R, 4 and 4x (I.P.
24, 34, 65)
 |
43000
Adc @ 266 vdc Chlorate Power Supply (86 Ka Set) |

Semiconductor
/ Transformer cooling:
• |
N
Class 1: Forced air cooling
|
• |
N
Class 2: Direct water cooling up to 50 volts dc |
• |
N
Class3: Convection - natural air |
• |
N
Class 4: Indirect cooling |
|
• |
air
to water on transformer |
|
• |
glycol
to water on semiconductor, sealed water cooled |
• |
N
Class 5: Indirect cooling |
|
• |
air
to water on transformer and semiconductors water cooled
|
• |
N
Class 6: Indirect cooling |
|
• |
air
to glycol on transformer
|
|
• |
glycol
to water on semiconductor, sealed air cooled |
• |
N
Class 7: Air conditioners |
• |
N
Class 7: Air conditioners |
• |
N
Class 8: Air to air heat exchangers |
• |
N
Class 9: Oil cooled OA |
• |
N
Class 10: ONAF |
• |
N
Class 11 :OFAF
|

Transformer:
Dry
type up to 24 Kv, 115 deg rise designed with 220 deg insulation
materials. Vacuum pressure impregnated. Copper wound. Oil
filled transformers available up to 34 Kv.

Power
Factor / Harmonic Correction
equipment available
Protection:
• |
Current
limiting fuses on each power semiconductor
|
• |
Trigger
fuse system |
• |
Thermal
devices on heat sinks and in transformer |
• |
Space
heaters to protect against moisture when the unit
is de-energized |
| • |
Leak
detector on water cooled units |
Instrumentation:
(example)
• |
DC
Voltmeter
|
• |
DC
Ammeter |
• |
Buss
Ground Meter |
• |
Digital
Ampere Hour Meter |
| • |
Annunciator
|
| • |
AC
Ammeter and Voltmeter |
| • |
PLC |
 |
Cathodic
Protection Unit |
|
15000
Adc @ 380 vdc Chlorate Power Supply |
|
|
103kA
@ 400 vdc 12 pulse system with Harmonic/Power Factor
correction
|
|
|
80kA
@ 280 vdc 12 pulse system with OLTC
|
|
16
MVA Transformer being loaded onto a truck |
|
|
Typical
Electrochemical Power Supply |
| |
144
ADC @ 400 VDC Water Processing Power Supply |
|
|
86,000
adc @ 400 vdc with HFC
|
|
|
OIL
TYPE COIL IN WINDING 35 MVA
|
|
|
Power
Factor / Harmonic Correction Substation
|
|
|
16.5
MVA Rectifier Transformer with Auto and OLTC
|